Scale 22 kW shaft power by a speed ratio of 0.8 cubed and multiply by the new annual hours. In the worked example, Annual operating hours at reduced speed of 3,000 h gives annual estimated shaft energy of 33.792 MWh.

Set up the field measurement

Build an operating-hours histogram from drive logs. A low-speed standby period can occupy many more hours than full production. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 2,000 h the calculated annual estimated shaft energy is 22.528 MWh. At 3,000 h it is 33.792 MWh. Subtracting the first output from the second gives 11.264 MWh. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Annual estimated shaft energy (MWh) plotted against annual operating hours at reduced speed (h). Across the example the output changes from 5.632 to 67.584.
Annual estimated shaft energy (MWh) plotted against annual operating hours at reduced speed (h). Across the example the output changes from 5.632 to 67.584. Figure by Industry Applied.

Worked data

Annual operating hours at reduced speed (h)

Annual estimated shaft energy (MWh)

500

5.632

1000

11.264

2000

22.528

3000

33.792

4000

45.056

6000

67.584

Checking the working range

At the two ends of the example, an input of 500 gives 5.632 and an input of 6,000 gives 67.584. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

The cube relation applies under similarity conditions. Use measured motor input in each speed band to prepare a purchase or annual energy budget. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy fan systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.