Multiply 8,760 hours by duty fraction, 7.5 kW average electrical load and an illustrative flat energy charge of A$0.21 per kWh. In the worked example, Share of the year operating of 35 % gives annual electricity cost of 4,828.9 AUD.

Set up the field measurement

Use a motor-run signal and meter the input while running. Sites with frequent starts may need time integration instead of one average reading. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 20 % the calculated annual electricity cost is 2,759.4 AUD. At 35 % it is 4,828.9 AUD. Subtracting the first output from the second gives 2,069.5 AUD. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Annual electricity cost (AUD) plotted against share of the year operating (%). Across the example the output changes from 689.85 to 11,038.
Annual electricity cost (AUD) plotted against share of the year operating (%). Across the example the output changes from 689.85 to 11,038. Figure by Industry Applied.

Worked data

Share of the year operating (%)

Annual electricity cost (AUD)

5

689.85

10

1379.7

20

2759.4

35

4828.95

50

6898.5

80

11037.6

Checking the working range

At the two ends of the example, an input of 5 gives 689.85 and an input of 80 gives 11,038. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

The example excludes demand and fixed charges, tariff windows and taxes. Replace the sample tariff with the applicable bill line before comparing options. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.