A temperature probe with a 20-second time constant can take about 46 seconds to register 90% of a sudden temperature change. A logger sampling it every second will capture the delay in detail. It cannot make the probe follow the water faster. Before using a trend to time a batch or compare two skids, determine the response of the whole measuring assembly under the process conditions of interest.
Read the percentage on the specification
Consider a mixing-water loop that moves from 20°C to 60°C in an ideal step. The step is 40°C. A probe has covered 63.2% of that change when it indicates roughly 45.3°C, and 90% when it indicates 56°C. Response specifications refer to a percentage of the change between the starting and final values. Using a percentage of 60°C gives entirely different thresholds.
In a first-order model the remaining difference from the final temperature is the starting difference multiplied by exp(−t/τ). The symbol τ represents the time constant. With τ = 20 seconds, after 20 seconds the indicated temperature is 45.28°C. After 40 seconds it is 54.59°C. It reaches 56°C at about 46.05 seconds and 58°C at about 59.91 seconds. Those latter figures correspond to 90% and 95% of this particular step.

Separate sensing delay from the process delay
Imagine two trend lines from an Australian food-packaging plant’s equipment-wash water rig. One sensor is immersed directly in a small test vessel. Another sits inside a protection pocket in a recirculation line. A difference in their arrival times might reflect the water’s journey to the second sensor, the pocket’s thermal mass, imperfect contact between the insert and pocket, or digital averaging in one transmitter. Assigning the full delay to a single probe would lead to a poor replacement specification.
For an agreed comparison, record the step reference and both outputs on the same clock. Record the medium, fluid movement, immersion depth, probe sheath and pocket assembly. Include transmitter damping and logger sample interval. Time each sensor from the observed change at its own location, if a suitable reference is available there. Where the local liquid temperature itself rises gradually, describe the trial as a response to a ramp. A slow reference cannot demonstrate a faster probe.
Compare assemblies in a representative test
A vendor may specify an exposed probe in flowing water while the installed sensor is protected and used in slower-moving liquid. Ask for the response percentage and the conditions to which the quoted time applies. A t90 value and a time constant cannot be directly compared until both the definition and response shape are understood. For a first-order response t90 is approximately 2.303 times τ. Multi-stage assemblies can depart noticeably from that relationship.
Use several points from the transient to check the approximation. If an observed sensor reaches 45.3°C in 20 seconds but takes 90 seconds to reach 56°C, one 20-second time constant is an inadequate description of the whole response. Record the actual time to the temperature that matters for this plant report. Preserve the raw trace before applying smoothing so an engineer can distinguish the instrument behaviour from later processing.
Worked data
Elapsed time (s) | Indication (°C) | Step completed (%) |
|---|---|---|
0.00 | 20.00 | 0.0 |
10.00 | 35.74 | 39.3 |
20.00 | 45.28 | 63.2 |
40.00 | 54.59 | 86.5 |
46.05 | 56.00 | 90.0 |
59.91 | 58.00 | 95.0 |
The worked data describe an ideal 20°C to 60°C first-order step. Download the time and temperature pairs. WIKA explains response-time benchmarks and installation conditions. The model is an illustration for interpreting normal equipment trends. A process acceptance test needs the actual assembly and its agreed decision criteria.
Cover photograph by Jakub Zerdzicki, published under the Pexels licence. The calculation, data and chart are by Industry Applied.