Across 619 qualifying US industrial recommendations, the median projected simple payback was 1.438 years. The middle half ran from 0.7278 to 2.71 years. Those figures describe the assessed proposals for outside-air HVAC economisers, in fiscal years 1993 to 2026.

The scope of the plant change

Build an hours-of-opportunity estimate using outside and return-air conditions during occupied cooling demand. Include intake pressure loss, damper feedback and humidity limits. Use the compressor and fan energy together in the comparison.

A recommendation you can reproduce

Recommendation KU050602 in US fiscal year 1998 pairs US$20,250 of implementation cost with US$14,080 in estimated annual net savings. Dividing the first figure by the second gives 1.438 years. This record was selected by proximity to the median payback, with the more recent assessment preferred when ratios tie.

The median implementation cost was US$6,000 and the median annual saving was US$4,656. Those two medians can come from different facilities. To obtain the payback distribution, divide cost by annual savings within each recommendation and take percentiles of the resulting years. Zero-cost measures remain in the calculation. The table selects actual records at five ordered positions, so its rounded examples can differ slightly from interpolated percentiles.

Estimated payback for outside-air HVAC economisers. Lower quartile 0.7278, median 1.438 and upper quartile 2.71 years.
Estimated payback for outside-air HVAC economisers. Lower quartile 0.7278, median 1.438 and upper quartile 2.71 years. Figure by Industry Applied.

What the records can support

The source lists 645 recommendations under assessment code 2.7241. The analysis retains records with a reported fiscal year, a non-negative implementation cost and positive net annual monetary savings. It sums the reported primary, secondary, tertiary and quaternary dollar savings, preserving recorded costs or offsets. A missing savings field contributes nothing only when at least one resource has a recorded value.

Of the 619 comparable records, 153 carry the implemented flag and 441 the non-implemented flag. The remaining 25 have another or unreported status. These are administrative outcomes. They do not establish the saving subsequently measured at an individual plant.

Worked data

Recommendation ID

US fiscal year

Implementation cost (USD)

Estimated annual net saving (USD)

Recalculated payback (years)

UA011701

2014

120

116327

0.001031575

SF034107

2007

15000

20686

0.7251281

KU050602

1998

20250

14080

1.43821

NC024805

2002

40000

14743

2.713152

UD109602

2024

114000

407

280.0983

Using the evidence in an Australian project

For the worked record, delivering only three quarters of its estimated annual saving would give 1.918 years. At full forecast savings and a 20% higher installed cost, it would give 1.726 years. These are sensitivity calculations using the same original proposal. A local business case needs quotations and a current Australian tariff or material price.

Reconcile the proposed baseline and the acceptance test in the same spreadsheet. Record the meter boundary, operating hours and product output in both periods. Keep any downtime allowance separate from recurring savings when comparing two options.

Sources and calculation files

The assessment-code results and the US Industrial Training and Assessment Centers database download contain the original recommendations. Dollar amounts are nominal US dollars for the assessment year. The Australian Government equipment guides provide local context. Download the worked records as CSV.