At 22 m head and a fixed combined efficiency of 68 percent, divide bypass hydraulic power by the assumed efficiency. At 6 on the bypass flow (l/s) scale, the worked result is 1.904 on the electrical power associated with bypass (kw) scale. The figure and table let you check the result against a second operating point.

Set up the field measurement

Measure bypass flow in the return leg while recording the normal operating point. A small return flow that persists overnight can matter more than a short peak. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

Compare the two adjacent inputs of 4 and 6 l/s. The calculation gives 1.269 at the first and 1.904 at the second. The signed change is 0.6345 on the output scale. A spreadsheet cross-check should reproduce both rows and the direction of change before it is copied through the remaining conditions.

Electrical power associated with bypass (kW) plotted against bypass flow (l/s). Across the example the output changes from 0.3173 to 3.807.
Electrical power associated with bypass (kW) plotted against bypass flow (l/s). Across the example the output changes from 0.3173 to 3.807. Figure by Industry Applied.

Worked data

Bypass flow (L/s)

Electrical power associated with bypass (kW)

1

0.317274

2

0.6345479

4

1.269096

6

1.903644

8

2.538192

12

3.807288

Checking the working range

At the two ends of the example, an input of 1 gives 0.3173 and an input of 12 gives 3.807. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

The calculation allocates power at a fixed head. Closing the bypass moves the duty point and requires a new measurement of the complete system. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.