Multiply the stated air changes per hour by a rectangular volume of 24 × 12 × 4 metres. In the worked example, Nominal air changes per hour 3 gives outdoor air volume of 3,456 m³/h.

Set up the field measurement

Measure the outside-air component. Recirculated air can add to the supply volume without refreshing the workshop air at the same rate. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 2 the calculated outdoor air volume is 2,304 m³/h. At 3 it is 3,456 m³/h. Subtracting the first output from the second gives 1,152 m³/h. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Outdoor air volume (m³/h) plotted against nominal air changes per hour. Across the example the output changes from 576 to 6,912.
Outdoor air volume (m³/h) plotted against nominal air changes per hour. Across the example the output changes from 576 to 6,912. Figure by Industry Applied.

Worked data

Nominal air changes per hour

Outdoor air volume (m³/h)

0.5

576

1

1152

2

2304

3

3456

4

4608

6

6912

Checking the working range

At the two ends of the example, an input of 0.5 gives 576 and an input of 6 gives 6,912. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

This is an arithmetic conversion only. Ventilation design for contaminants or occupancy requires the applicable engineering criteria for the space. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy fan systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.