At 2.4 cubic metres per second, multiply additional pressure by airflow and divide by 60 percent combined efficiency. In the worked example, Additional filter pressure drop of 100 Pa gives additional input power of 0.4 kW.

Set up the field measurement

Compare clean and loaded filter measurements at the same measured airflow. A fixed-speed fan can deliver less air as the filter loads. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 75 Pa the calculated additional input power is 0.3 kW. At 100 Pa it is 0.4 kW. Subtracting the first output from the second gives 0.1 kW. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Additional input power (kW) plotted against additional filter pressure drop (pa). Across the example the output changes from 0.1 to 0.8.
Additional input power (kW) plotted against additional filter pressure drop (pa). Across the example the output changes from 0.1 to 0.8. Figure by Industry Applied.

Worked data

Additional filter pressure drop (Pa)

Additional input power (kW)

25

0.1

50

0.2

75

0.3

100

0.4

150

0.6

200

0.8

Checking the working range

At the two ends of the example, an input of 25 gives 0.1 and an input of 200 gives 0.8. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

The example holds flow and efficiency constant. A pressure-only change cannot establish the electrical saving without the actual control response. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy fan systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.