Divide pressure in pascals by a water density of 998 kg per cubic metre and standard gravity. In the worked example, Differential pressure of 75 kPa gives water head of 7.6632 m.

Set up the field measurement

Record which tap supplies each side of the transmitter. If the tapping points differ in elevation, include that information in a total-head calculation. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 50 kPa the calculated water head is 5.1088 m. At 75 kPa it is 7.6632 m. Subtracting the first output from the second gives 2.5544 m. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Water head (m) plotted against differential pressure (kpa). Across the example the output changes from 1.022 to 15.326.
Water head (m) plotted against differential pressure (kpa). Across the example the output changes from 1.022 to 15.326. Figure by Industry Applied.

Worked data

Differential pressure (kPa)

Water head (m)

10

1.02176

25

2.554399

50

5.108799

75

7.663198

100

10.2176

150

15.3264

Checking the working range

At the two ends of the example, an input of 10 gives 1.022 and an input of 150 gives 15.326. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

A density change changes the metres of liquid represented by a given pressure. Keep gauge pressure and differential pressure identifiable. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.