Divide 24 cubic metres of active tank volume by throughput and convert hours to minutes. In the worked example, Steady throughput of 18 m³/h gives nominal residence time of 80 min.

Set up the field measurement

Separate the active volume from dead storage below the outlet. Record the operating water level at the time of the flow test. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 12 m³/h the calculated nominal residence time is 120 min. At 18 m³/h it is 80 min. Subtracting the first output from the second gives -40 min. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Nominal residence time (min) plotted against steady throughput (m³/h). Across the example the output changes from 240 to 40.
Nominal residence time (min) plotted against steady throughput (m³/h). Across the example the output changes from 240 to 40. Figure by Industry Applied.

Worked data

Steady throughput (m³/h)

Nominal residence time (min)

6

240

10

144

12

120

18

80

24

60

36

40

Checking the working range

At the two ends of the example, an input of 6 gives 240 and an input of 36 gives 40. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

Mixing and short-circuiting spread actual residence times. A tracer test answers a different question from this nominal volume-to-flow ratio. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.