Subtract a simultaneous 3 L/s outflow and divide net litres per minute by 12 square metres of plan area. In the worked example, Pump inflow of 6 L/s gives rise rate after continuous outflow of 15 mm/min.

Set up the field measurement

A negative result predicts falling level. Verify the area at the working height if the sump has a sloping floor or sloping sides. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 4 L/s the calculated rise rate after continuous outflow is 5 mm/min. At 6 L/s it is 15 mm/min. Subtracting the first output from the second gives 10 mm/min. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Rise rate after continuous outflow (mm/min) plotted against pump inflow (l/s). Across the example the output changes from -5 to 45.
Rise rate after continuous outflow (mm/min) plotted against pump inflow (l/s). Across the example the output changes from -5 to 45. Figure by Industry Applied.

Worked data

Pump inflow (L/s)

Rise rate after continuous outflow (mm/min)

2

-5

3

0

4

5

6

15

9

30

12

45

Checking the working range

At the two ends of the example, an input of 2 gives -5 and an input of 12 gives 45. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

Compare the slope over a full sample interval. A bouncing float or turbulent water surface can create apparent changes much larger than the average rise. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.