Multiply mean velocity by an unobstructed rectangular duct area of 0.45 by 0.30 metres and then by 3,600. In the worked example, Mean cross-sectional air speed of 4 m/s gives duct volume flow of 1,944 m³/h.

Set up the field measurement

Use a traversal that represents the duct cross section and allow for a liner or obstruction when calculating the open area. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.

Two operating points

At 3 m/s the calculated duct volume flow is 1,458 m³/h. At 4 m/s it is 1,944 m³/h. Subtracting the first output from the second gives 486 m³/h. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Duct volume flow (m³/h) plotted against mean cross-sectional air speed (m/s). Across the example the output changes from 486 to 2,916.
Duct volume flow (m³/h) plotted against mean cross-sectional air speed (m/s). Across the example the output changes from 486 to 2,916. Figure by Industry Applied.

Worked data

Mean cross-sectional air speed (m/s)

Duct volume flow (m³/h)

1

486

2

972

3

1458

4

1944

5

2430

6

2916

Checking the working range

At the two ends of the example, an input of 1 gives 486 and an input of 6 gives 2,916. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.

Interpreting the result

One centreline reading can overstate the mean. Swirl and distorted profiles close to elbows complicate the comparison. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.

Source and calculation data

For the underlying measurement context, see the US Department of Energy fan systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.