Multiply the 30 kW reference shaft power by the cube of the speed ratio under similarity conditions. In the worked example, Speed as a fraction of reference of 85 % gives indicative shaft power of 18.424 kW.
Set up the field measurement
Log head, flow and speed together at several stable points. Strong static lift changes the system curve and a similar pump operating point may no longer exist. Keep the reference observation alongside the calculation, with the instrument identification, observation period and units. This makes it possible for the next shift to distinguish a new operating condition from a change in how the observation was recorded.
Two operating points
At 80 % the calculated indicative shaft power is 15.36 kW. At 85 % it is 18.424 kW. Subtracting the first output from the second gives 3.0637 kW. These values give two independent checkpoints for a spreadsheet or a logger conversion.

Worked data
Speed as a fraction of reference (%) | Indicative shaft power (kW) |
|---|---|
60 | 6.48 |
70 | 10.29 |
80 | 15.36 |
85 | 18.42375 |
90 | 21.87 |
100 | 30 |
Checking the working range
At the two ends of the example, an input of 60 gives 6.48 and an input of 100 gives 30. Use a value near each end to check your implementation. Testing only the middle row can conceal an incorrect offset, an inverted ratio or a unit conversion applied twice.
Interpreting the result
Drive losses and motor efficiency affect electrical input. Treat this as a shaft-power comparison and measure the electrical difference separately. If measured performance sits outside the worked range, first repeat the comparison using field inputs and the same boundary. Preserve the original reading in the export. A discrepancy is easier to investigate when the field observation and the calculated output occupy separate columns.
Source and calculation data
For the underlying measurement context, see the US Department of Energy pumping systems sourcebook. The operating values and sensitivity analysis here are an Industry Applied worked example. Download the input and output values to verify the calculation with the values from your own site.