The hex.ele[1].mas.T trace covers 10.565 to 20 °C, a temperature span of 9.435 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named WetCoilCounterFlowLowWaterFlowRate. The source file places it under Fluid, Heat Exchangers. We used the 101 stored values for hex.ele[1].mas.T over the interval 0 to 5,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name hex (Wet Coil Counter Flow), sou_w (Mass Flow Source T), sin_w (Boundary p T), sou_a (Mass Flow Source T). The source declares mWat_flow_nominal = 0.44732114, mAir_flow_nominal = 0.65844. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel hex.Q1_flow starts at 0, ends at 0.004035 and has a recorded range of 0 to 1,334 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Wet coil counter flow low water flow rate. The simulated hex.ele[1].mas.T channel runs from 283.715 to 293.15 K over 5,000 seconds.
Wet coil counter flow low water flow rate. The simulated hex.ele[1].mas.T channel runs from 283.715 to 293.15 K over 5,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 50 seconds. Subtracting 293.15 from 283.771 gives -9.379 K. Its location brackets the change within one saved interval of 50 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hex.ele[1].mas.T (K)

hex.Q1_flow (W)

0

293.15

0

50

283.7708

1327.253

150

283.7151

1334.218

1000

283.7517

1297.52

2000

284.3099

776.0297

3000

285.1031

24.87811

4000

285.1491

0.3321163

5000

285.15

0.004035363

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.