The recorded tang.V_flow channel spans 0 to 0.4759 m³/s in this reference run. It starts at 0.4456 and ends at 0.4759. The first recorded maximum occurs at 171 seconds and the first minimum at 90 seconds.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named VentilationFlowRateSimpleOpening. The source file places it under Airflow, Window Ventilation. We used the 101 stored values for tang.V_flow over the interval 0 to 180 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name TRoomSet (Ramp), from_degC (From deg C), TAmbSet (Ramp), from_degC1 (From deg C). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel TAmbSet.y starts at 40, ends at 0 and has a recorded range of 0 to 40 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
Integrating the signed rate over 180 seconds gives a net 59.981 m³. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | tang.V_flow (m³/s) | TAmbSet.y (source units) |
|---|---|---|
0 | 0.4456287 | 40 |
36 | 0.383427 | 33.5 |
72 | 0.2312301 | 24.5 |
88.2 | 0.09545488 | 20.45 |
90 | 0 | 20 |
108 | 0.2294748 | 15.5 |
144 | 0.3931907 | 6.5 |
171 | 0.4758979 | 0 |
180 | 0.4758979 | 0 |
What to check on site
Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.