The recorded hall.V_flow channel spans 0 to 0.2266 m³/s in this reference run. It starts at 0 and ends at 0.2266. The first recorded maximum occurs at 180 seconds and the first minimum at 0 seconds.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named VentilationFlowRateSashOpening. The source file places it under Airflow, Window Ventilation. We used the 101 stored values for hall.V_flow over the interval 0 to 180 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name TRoomSet (Ramp), from_degC (From deg C), TAmbSet (Ramp), from_degC1 (From deg C). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel maas.V_flow covers 0 to 0.6325 m³/s. At 109.8 s, the primary value is 0.1126 and the companion is 0.6325. Their signed difference is -0.5199 m³/s, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
Integrating the signed rate over 180 seconds gives a net 7.825 m³. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | hall.V_flow (m³/s) | maas.V_flow (m³/s) |
|---|---|---|
0 | 0 | 0 |
36 | 0 | 0 |
72 | 0 | 0.1130913 |
108 | 0.09231952 | 0.4364521 |
144 | 0.08297008 | 0.07200269 |
169.2 | 0.2127951 | 0.170049 |
171 | 0.02149406 | 0.02022054 |
180 | 0.2265825 | 0.1831016 |
What to check on site
Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.