The con.TZon trace covers 14.941 to 25.031 °C, a temperature span of 10.09 K. The first recorded maximum occurs at 302,400 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Guideline36. The source file places it under Air, Systems, Single Zone, variable air volume. We used the 101 stored values for con.TZon over the interval 0 to 864,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name hysChiPla (Hysteresis), errTRooCoo (Feedback), occSch (Occupancy Schedule), uWin (Boolean Constant). The source declares TSupChi_nominal = 279.15. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel con.TZonCooSet starts at 303.15, ends at 303.15 and has a recorded range of 298.15 to 303.15 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

VAV guideline36. The simulated con.TZon channel runs from 288.091 to 298.181 K over 864,000 seconds.
VAV guideline36. The simulated con.TZon channel runs from 288.091 to 298.181 K over 864,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 803,520 to 812,160 seconds. Subtracting 288.164 from 297.717 gives 9.554 K. Its location brackets the change within one saved interval of 8,640 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

con.TZon (K)

con.TZonCooSet (source units)

0

293.15

303.15

172800

288.1502

303.15

302400

298.1812

298.15

328320

288.0909

303.15

345600

288.1473

303.15

518400

288.1526

303.15

691200

288.1437

303.15

803520

288.1639

303.15

812160

297.7174

298.15

864000

288.1439

303.15

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.