The signed flow trace gives a net 370.743 kg over 3,600 s, using the trapezoidal rule between saved samples. The smallest and largest reported rates are 0.021978 kg/s and 0.15291 kg/s. Check the positive flow direction in the model before using the sign to describe delivery or return.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named VAVBoxReheat. The source file places it under Templates, Zone Equipment. We used the 101 stored values for VAVBox_1.damVAV.m_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.
The reference file contains 4 recorded variables. Alongside the primary output there are VAVBox_1.bus.TAirSup, VAVBox_1.bus.TAirDis, VAVBox_1.bus.TZon, VAVBox_1.damVAV.m_flow. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.
Compare the recorded channels
The primary channel spends 80.2% of its saved checkpoints at or above 0.08744 kg/s, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 0.103 kg/s. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Reproduce the calculation
Integrating the signed rate over 3,600 seconds gives a net 370.743 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | VAVBox_1.damVAV.m_flow (kg/s) |
|---|---|
0 | 0.1529114 |
36 | 0.07524334 |
72 | 0.02197753 |
720 | 0.08604357 |
1440 | 0.1110156 |
2160 | 0.1176986 |
2880 | 0.119527 |
3600 | 0.1200346 |
What to check on site
Compare fuel or electrical input with useful heat at a declared delivery boundary. Include the warm-up interval and any period on standby. Separate a temperature setpoint from the measured outlet and keep auxiliary energy in a stated part of the balance.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.