The recorded VAVBox_1.damVAV.m_flow channel spans 0.01416 to 0.1529 kg/s in this reference run. It starts at 0.1529 and ends at 0.12. The first recorded maximum occurs at 0 seconds and the first minimum at 108 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named VAVBoxCoolingOnly. The source file places it under Templates, Zone Equipment. We used the 101 stored values for VAVBox_1.damVAV.m_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name bouPri (Boundary p T), bouBui (Boundary p T), sigBAS (BAS Control Points). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 79.2% of its saved checkpoints at or above 0.08354 kg/s, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 0.09996 kg/s. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Variable air volume terminal unit cooling only. The simulated VAVBox_1.damVAV.m_flow channel runs from 0.01416 to 0.1529 kg/s over 3,600 seconds.
Variable air volume terminal unit cooling only. The simulated VAVBox_1.damVAV.m_flow channel runs from 0.01416 to 0.1529 kg/s over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 3,600 seconds gives a net 359.848 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

VAVBox_1.damVAV.m_flow (kg/s)

0

0.1529114

36

0.07524334

108

0.01416349

720

0.08031442

1440

0.1094763

2160

0.1172802

2880

0.1194129

3600

0.1200052

What to check on site

Identify which part of the system the selected output represents, and retain the surrounding boundary conditions. Compare the same event and operating duty in both records. Record the equipment configuration if a later change could alter the test result.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.