The solCol.vol[3].T trace covers 8.936 to 27.676 °C, a temperature span of 18.74 K. The first recorded maximum occurs at 51,840 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named FlatPlateTotalArea. The source file places it under Fluid, Solar Collectors. We used the 101 stored values for solCol.vol[3].T over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name solCol (ASHRAE93), weaDat (Reader TMY3), sin (Boundary p T), TOut (Temperature Two Port). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel solCol.vol[6].T covers 281.224 to 315.226 K. At 51,840 s, the primary value is 300.826 and the companion is 315.226. Their signed difference is -14.4 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.
![Use of total area and n seg. The simulated solCol.vol[3].T channel runs from 282.086 to 300.826 K over 86,400 seconds.](https://static.wixstatic.com/media/21e41b_5908193748b843929453ec175d2cd839~mv2.png/v1/fill/w_616,h_345,al_c,q_85,enc_auto/21e41b_5908193748b843929453ec175d2cd839~mv2.png)
Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 864 seconds. Subtracting 293.15 from 284.547 gives -8.603 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | solCol.vol[3].T (K) | solCol.vol[6].T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
864 | 284.5474 | 288.5192 |
17280 | 282.2156 | 281.5045 |
19872 | 282.086 | 281.2252 |
34560 | 293.7498 | 301.539 |
51840 | 300.8256 | 315.2257 |
69120 | 283.2564 | 283.3521 |
86400 | 282.5623 | 282.1062 |
What to check on site
Check the time reference, location and receiving plane for each environmental input. Two measured series can differ because one records horizontal exposure and the other a tilted surface. A comparison needs the same averaging interval and geometric definition.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.