The recorded hydraulicBus.TFwrdInMea channel spans 303.078 to 323.15 source units in this reference run. It starts at 303.15 and ends at 323.15. The first recorded maximum occurs at 408 seconds and the first minimum at 180 seconds.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named ThrottlePump. The source file places it under Systems, Hydraulic Modules. We used the 101 stored values for hydraulicBus.TFwrdInMea over the interval 0 to 600 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name hydRes (Pressure Drop). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The two named channels have separate paths in the model. hydraulicBus.TFwrdInMea begins at 303.15 and ends at 323.15. hydraulicBus.TFwrdOutMea begins at 303.15 and ends at 323.16. The reference export supplies numerical samples but does not attach a physical unit to these fields. Use the linked model declarations to establish the quantity and units of each channel before calculating a difference or assigning it a physical meaning.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 186 to 192 seconds. Subtracting 305.472 from 311.183 gives 5.711 source units. Its location brackets the change within one saved interval of 6 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | hydraulicBus.TFwrdInMea (source units) | hydraulicBus.TFwrdOutMea (source units) |
|---|---|---|
0 | 303.15 | 303.15 |
120 | 303.1039 | 303.1029 |
180 | 303.0779 | 303.0762 |
186 | 305.4719 | 303.0817 |
192 | 311.183 | 303.0987 |
240 | 322.6622 | 304.4275 |
360 | 323.1498 | 323.0781 |
408 | 323.15 | 323.1532 |
480 | 323.15 | 323.1569 |
600 | 323.15 | 323.1566 |
What to check on site
Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.