The TSoi[1].T trace covers -0.4847 to 22.645 °C, a temperature span of 23.13 K. The first recorded maximum occurs at 17,975,520 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named UndisturbedSoilTemperature. The source file places it under Boundary Conditions, Ground Temperature. We used the 101 stored values for TSoi[1].T over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The source declares nSoi = 4. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TSoi[2].T covers 278.376 to 290.084 K. At 31,220,640 s, the primary value is 273.947 and the companion is 281.876. Their signed difference is -7.929 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Undisturbed soil temperature. The simulated TSoi[1].T channel runs from 272.665 to 295.795 K over 31,536,000 seconds.
Undisturbed soil temperature. The simulated TSoi[1].T channel runs from 272.665 to 295.795 K over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 25,544,160 to 25,859,520 seconds. Subtracting 284.642 from 283.916 gives -0.7264 K. Its location brackets the change within one saved interval of 315,360 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TSoi[1].T (K)

TSoi[2].T (K)

0

273.6154

281.523

2207520

272.6653

279.5708

6307200

276.5641

278.4543

1.26144e+07

290.0946

283.3583

1.797552e+07

295.7954

288.8818

1.89216e+07

295.5297

289.4656

2.52288e+07

285.3669

288.3458

2.554416e+07

284.6422

288.0763

2.585952e+07

283.9158

287.7917

3.1536e+07

273.6347

281.5446

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.