The recorded valCv.m_flow channel spans 2.81e-07 to 0.4 kg/s in this reference run. It starts at 2.81e-07 and ends at 0.4. The first recorded maximum occurs at 1 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TwoWayValveParameterization. The source file places it under Fluid, Actuators, Valves. We used the 101 stored values for valCv.m_flow over the interval 0 to 1 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name valOpePoi (Two Way Linear), y (Ramp), valKv (Two Way Linear), valCv (Two Way Linear). The source declares m_flow_nominal = 0.4, dp_nominal = 4500. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 50.5% of its saved checkpoints at or above 0.2 kg/s, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 0.2 kg/s. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Two-way valve parameterization. The simulated valCv.m_flow channel runs from 2.81e-07 to 0.4 kg/s over 1 seconds.
Two-way valve parameterization. The simulated valCv.m_flow channel runs from 2.81e-07 to 0.4 kg/s over 1 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 1 seconds gives a net 0.2 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

valCv.m_flow (kg/s)

0

2.8125e-07

0.01

0.002795217

0.02

0.0080392

0.2

0.080032

0.4

0.160024

0.6

0.240016

0.8

0.320008

1

0.4

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.