The senTemChWIn.T trace covers 8.001 to 11.999 °C, a temperature span of 3.997 K. The first recorded maximum occurs at 50,457,600 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TwoBuriedPipes. The source file places it under Fluid, Fixed Resistances, Buried Pipes. We used the 101 stored values for senTemChWIn.T over the interval 0 to 63,072,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name cliCon (Boston), gro (Ground Coupling), pipChW (Plug Flow Pipe), TinChW (Sine). The source declares TChW = 273.15 + 10, THotW = 273.15 + 80. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTemChWOut.T covers 283.15 to 288.876 K. At 53,611,200 s, the primary value is 283.801 and the companion is 287.884. Their signed difference is -4.083 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Two buried pipes in close proximity. The simulated senTemChWIn.T channel runs from 281.151 to 285.149 K over 63,072,000 seconds.
Two buried pipes in close proximity. The simulated senTemChWIn.T channel runs from 281.151 to 285.149 K over 63,072,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 61,810,560 to 62,441,280 seconds. Subtracting 282.83 from 283.338 gives 0.508 K. Its location brackets the change within one saved interval of 630,720 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTemChWIn.T (K)

senTemChWOut.T (K)

0

283.15

283.15

1.26144e+07

281.2956

284.8731

2.52288e+07

281.7607

285.6383

2.712096e+07

281.1515

285.0702

3.78432e+07

283.9635

286.2914

5.04576e+07

285.1488

288.7336

6.181056e+07

282.8302

285.9638

6.244128e+07

283.3382

286.1569

6.3072e+07

283.834

286.3553

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.