The recorded trimRespondLogic.y channel spans 110 to 370 source units in this reference run. It starts at 120 and ends at 370. The first recorded maximum occurs at 1,728 seconds and the first minimum at 432 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TrimAndRespond. The source file places it under Controls, OBC, ASHRAE, G36, Generic. We used the 101 stored values for trimRespondLogic.y over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name trimRespondLogic (Trim And Respond), trimRespondLogic1 (Trim And Respond), trimRespondLogic2 (Trim And Respond), con (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel trimRespondLogicHold.y covers 110 to 370 source units. At 1,728 s, the primary value is 370 and the companion is 233. Their signed difference is 137 source units, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Trim and respond block. The simulated trimRespondLogic.y channel runs from 110 to 370 source units over 7,200 seconds.
Trim and respond block. The simulated trimRespondLogic.y channel runs from 110 to 370 source units over 7,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 792 to 864 seconds. Subtracting 165 from 192 gives 27 source units. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

trimRespondLogic.y (source units)

trimRespondLogicHold.y (source units)

0

120

120

432

110

110

792

165

125

864

192

125

1440

300

206

1728

370

233

2880

330

322

4320

370

370

5760

310

330

7200

370

370

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.