A remote logger protects a water record through a mobile outage only if it can store every required observation and send the backlog while new observations continue to arrive. Ask for usable record capacity, the meaning of one record and sustained replay speed. A specification that simply says “stores 10,000 readings” leaves all three questions open.

Translate an outage into records

Consider a hypothetical Australian irrigation scheme monitoring six values at a remote pump station. The team wants one observation of every value every five minutes, with seven days of local history during a communications outage. There are 12 scans per hour and 288 per day. Over a week the logger must retain 2,016 scans. If the manufacturer counts each channel value as a reading, the same week uses 12,096 readings. A claim of 10,000 would then cover only about 5.8 days. If a reading instead means one complete six-channel scan, the quoted capacity covers more than a month.

Calculate the storage in the format actually written

Suppose the logger writes a 24-byte time and status header followed by six four-byte values. In this illustrative design the full scan is 48 bytes. Seven days need 2,016 × 48 = 96,768 bytes. A different design writes a separate 32-byte timestamped record for every channel. It uses 2,016 × 6 × 32 = 387,072 bytes for the same observations. A 25% design allowance takes those estimates to 120,960 and 483,840 bytes respectively. These are decimal bytes of record payload. The allowance is a purchasing assumption, and the manufacturer still needs to account for files, indexes, alarms, diagnostics and reserved space.

Illustrative six-channel, five-minute records. Seven days use 96,768 bytes when packed or 387,072 bytes in separate records, before storage overhead.
Illustrative six-channel, five-minute records. Seven days use 96,768 bytes when packed or 387,072 bytes in separate records, before storage overhead. Chart by Industry Applied.

Campbell Scientific’s CR300 documentation describes data tables with individual records and a configurable allocation. This is a reason to ask how the particular programme divides memory between tables. For an Australian example of documented fields, WaterNSW’s logged data format guidelines identify timestamped records issued to the Data Acquisition Service. A site assessing a regulated installation should check its applicable requirements directly. This worked example sizes an operations logger for an assumed service gap.

Recovery speed is a second capacity limit

Assume the link returns with 2,016 stored scans and can deliver 12 complete scans per minute, including acknowledgements. New scans arrive at 0.2 per minute. The net drain rate is 11.8 per minute, giving about 171 minutes to clear the backlog. A dashboard can show a current value after the first successful upload while nearly three hours of replay still lies ahead. If the receiver accepts records more slowly than the logger creates them, the backlog can continue growing even with the connection up.

What to put in an acceptance test

  • Specify whether timestamps represent sampling time or upload time, and use a record number or equivalent identifier to check for missing and repeated records after replay.

  • During a planned bench test, retain sensor power and interrupt the test communications path. Record a known changing input and a stable input. Check the local file contains both series, including the first and last expected timestamps.

  • Restore the test link and export the receiver history after replay. Compare the expected 12 scans per hour with the unique samples actually present. Record any clock correction, duplicate or missing interval.

  • Ask how the logger behaves when space fills and when site power fails. A communications buffer only protects readings the instrument had power to collect. Define a visible gap marker for a real sampling interruption.

A procurement brief can now name the number of channels, the scan interval, the outage duration, the minimum complete records and the allowed recovery time. A supplier can demonstrate each item with a sample export. The resulting record is far easier to interpret than a screenshot of a green connection icon.

Sources and working data

Campbell Scientific Australia’s guide to data tables describes how a logger organises records. WaterNSW’s logged data format guidelines provide a local format example. Download the seven-day storage calculations.

Cover photograph by Mattinbgn, published under the CC BY 3.0. The layout may crop the photograph. The worked example and chart are by Industry Applied.