For an eight-metre level transmitter, a nominal 12-bit input measuring 0–20 mA represents roughly 2.44 mm per ideal converter step over the active 4–20 mA signal. The same converter using its full code range for 4–20 mA would give about 1.95 mm per step. The smaller number describes finer digital increments. Actual uncertainty also comes from the transmitter, input electronics, wiring environment and how the level reference was established.

Start from the range the converter digitises

An ideal N-bit converter has 2ᴺ possible output codes. For a first estimate of the quantisation step, divide the full input range by 2ᴺ. A 12-bit input covering 0–20 mA has 4,096 codes and a nominal step of 20 ÷ 4,096 = 0.004883 mA, about 4.88 microamps. The level transmitter changes by 16 mA between empty and eight metres. Its sensitivity is therefore 2.00 mA per metre. Dividing the current step by that sensitivity gives 0.002441 m, or about 2.44 mm.

Only four fifths of a 0–20 mA input range corresponds to the transmitter’s normal 4–20 mA span. Selecting a 4–20 mA engineering scale in a display may merely change the labels assigned to existing raw counts. Read the analogue input documentation to see whether it changes the physical measuring range, the reported code span, or only the software conversion.

For an 8 m tank, ideal increments of 9.77, 2.44 and 1.95 mm result from a 10-bit 0–20 mA, 12-bit 0–20 mA and true 12-bit 4–20 mA input respectively.
For an 8 m tank, ideal increments of 9.77, 2.44 and 1.95 mm result from a 10-bit 0–20 mA, 12-bit 0–20 mA and true 12-bit 4–20 mA input respectively. Chart by Industry Applied.

Compare the options on the same level span

On an ideal 10-bit 0–20 mA input the step is 20 ÷ 1,024 = 0.019531 mA and the level increment is 9.77 mm. On the 12-bit range the 2.44 mm result is four times finer. A true 12-bit converter dedicating its entire range to the 16 mA of signal would give 16 ÷ 4,096 = 0.003906 mA, equivalent to 1.95 mm. At either end of a real module’s specified range, reserved diagnostic codes, overrange and endpoint conventions can affect the exact mapping. Use the manufacturer’s raw endpoints when setting the PLC scale.

A level transmitter with a hypothetical ±0.25% of eight metres span specification already contributes a ±20 mm error limit under the stated test conditions. An additional digit on the dashboard cannot establish a two-millimetre absolute level accuracy in that system. Conversely, finer repeatable resolution can still be valuable when looking for a small change around a stable operating point. Keep the required change detection and required absolute level accuracy as separate tender criteria.

Validate the entire record from milliamps to millimetres

During an authorised input simulation or bench test, record the input reading, raw count, PLC engineering value and historian value at several points. Include a midpoint and values either side of it. On a nominal 0–8 m span the 12 mA midpoint represents 4 m. If raw counts change while the historian holds the same rounded centimetre value, the historian’s rounding or deadband has become the limiting stage.

For an outdoor storage tank, the installed measurement also depends on how the transmitter senses level. When a hydrostatic device is used, density and reference elevation can matter. In a float or radar system the mechanical and geometric terms are different. Put those terms beside electrical quantisation in the measurement budget before replacing an input module solely on its advertised bit count.

Worked data

Nominal bits

Physical input range (mA)

Current step (µA)

Equivalent level step (mm)

10

0–20

19.5312

9.7656

12

0–20

4.8828

2.4414

12

4–20

3.9062

1.9531

14

0–20

1.2207

0.6104

Download the ideal converter comparisons. Analog Devices’ data conversion handbook explains ideal converter quantisation. Its current-loop application note describes different current-loop ranges. The worked figures use ideal step sizes, with no claim of a particular module’s calibrated accuracy.

Cover photograph by IT services EU, published under the Pexels licence. The calculation, data and chart are by Industry Applied.