The recorded oriEasTop.dp channel spans -35.211 to -0.1873 Pa in this reference run. It starts at -35.211 and ends at -0.1873. The first recorded maximum occurs at 792 seconds and the first minimum at 0 seconds.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named ThreeRoomsContamDiscretizedDoor. The source file places it under Airflow, Multizone. We used the 101 stored values for oriEasTop.dp over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name open1 (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel oriWesTop.dp covers -0.1873 to 34.916 Pa. At 0 s, the primary value is -35.211 and the companion is 34.916. Their signed difference is -70.127 Pa, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Three rooms contam discretized door. The simulated oriEasTop.dp channel runs from -35.211 to -0.1873 Pa over 3,600 seconds.
Three rooms contam discretized door. The simulated oriEasTop.dp channel runs from -35.211 to -0.1873 Pa over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 36 seconds. Subtracting -35.211 from -0.1873 gives 35.024 Pa. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

oriEasTop.dp (Pa)

oriWesTop.dp (Pa)

0

-35.21093

34.91569

36

-0.1872511

-0.1872512

720

-0.1872509

-0.1872514

792

-0.1872509

-0.1872514

1440

-0.1872511

-0.1872512

2160

-0.1872511

-0.1872512

2880

-0.1872511

-0.1872512

3600

-0.1872512

-0.1872512

What to check on site

Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.