The thermalZoneThreeElements.TAir trace covers 17.998 to 46.95 °C, a temperature span of 28.952 K. The first recorded maximum occurs at 13,875,840 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named SimpleRoomThreeElements. The source file places it under Thermal Zones, Reduced Order. We used the 101 stored values for thermalZoneThreeElements.TAir over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name weaDat (Reader TMY3), corGDouPan (Correction G Double Pane), thermalZoneThreeElements (Three Elements), eqAirTemp (VDI6007 With Window). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 53.5% of its saved checkpoints at or above 305.624 K, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 305.478 K. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Thermal zone with three heat conduction elements. The simulated thermalZoneThreeElements.TAir channel runs from 291.148 to 320.1 K over 31,536,000 seconds.
Thermal zone with three heat conduction elements. The simulated thermalZoneThreeElements.TAir channel runs from 291.148 to 320.1 K over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 11,352,960 to 11,668,320 seconds. Subtracting 317.84 from 308.694 gives -9.146 K. Its location brackets the change within one saved interval of 315,360 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

thermalZoneThreeElements.TAir (K)

0

295.15

630720

291.1479

6307200

303.792

1.135296e+07

317.8396

1.166832e+07

308.6935

1.26144e+07

310.9122

1.387584e+07

320.1003

1.89216e+07

313.9355

2.52288e+07

304.2649

3.1536e+07

293.2507

What to check on site

Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.