The temperature separation during tank cycling starts at 20 °C and finishes at 40 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 19.992 °C and 40.004 °C.
What the reference test measures
The Buildings model named StratifiedLoadingUnloading comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 14,400 seconds. Industry Applied extracted 101 checkpoints for tanEnh.vol[1].T and kept the original signed values. The regular output spacing is 144 seconds. The solver may take different internal steps.
The model definition identifies tanEnh (Stratified Enhanced), tan (Stratified), HIn_flow (Enthalpy Flow Rate). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Reading the two channels
At 11,520 seconds, tanEnh.vol[1].T is 312.552 and tanEnh.vol[7].T is 293.906. Subtracting the second channel from the first gives +18.646 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.
![Temperature separation during tank cycling. In the simulated StratifiedLoadingUnloading case, tanEnh.vol[1].T ranges from 293.142 to 313.154 K over 14,400 seconds.](https://static.wixstatic.com/media/21e41b_46e90a02ee43477cae6e95f03d6404ae~mv2.png/v1/fill/w_616,h_345,al_c,q_85,enc_auto/21e41b_46e90a02ee43477cae6e95f03d6404ae~mv2.png)
Reproducing the largest recorded change
Between the stored points at 10,800 and 10,944 seconds, tanEnh.vol[1].T changes from 293.142 to 303.244. Subtracting the earlier reading gives +10.102 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | tanEnh.vol[1].T (K) | tanEnh.vol[7].T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
3600 | 293.15 | 293.15 |
6192 | 313.1544 | 312.871 |
7200 | 313.1504 | 313.1579 |
10800 | 293.1421 | 293.1495 |
10944 | 303.2441 | 293.1486 |
14400 | 313.1505 | 313.1579 |
Applying the result to an operating site
Simultaneous readings at separated layers show the passage of a temperature front. Bulk-average tank temperature can stay plausible even when available outlet temperature changes sharply. Include the direction of loading and the position of each probe.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Daniel Dan, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.