The tank temperature for two exchanger locations starts at 20 °C and finishes at 58.459 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 20 °C and 58.459 °C.

What the reference test measures

The Buildings model named HeatExchangerLocation comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 600,000 seconds. Industry Applied extracted 101 checkpoints for tan_aTop.vol[1].T and kept the original signed values. The regular output spacing is 6,000 seconds. The solver may take different internal steps.

The model definition identifies tan_aTop (Tank), tan_bTop (Tank), watInTan (Boundary p T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares senTan_aTop.tau = 0, senTan_bTop.tau = 0. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 264,000 seconds, tan_aTop.vol[1].T is 323.812 and tan_bTop.vol[1].T is 323.33. Subtracting the second channel from the first gives +0.482 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Tank temperature for two exchanger locations. In the simulated HeatExchangerLocation case, tan_aTop.vol[1].T ranges from 293.15 to 331.609 K over 600,000 seconds.
Tank temperature for two exchanger locations. In the simulated HeatExchangerLocation case, tan_aTop.vol[1].T ranges from 293.15 to 331.609 K over 600,000 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 6,000 and 12,000 seconds, tan_aTop.vol[1].T changes from 294.341 to 295.637. Subtracting the earlier reading gives +1.296 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

tan_aTop.vol[1].T (K)

tan_bTop.vol[1].T (K)

0

293.15

293.15

6000

294.3413

294.3347

12000

295.6369

295.6302

150000

315.7006

315.3485

300000

325.475

325.0003

450000

329.7349

329.3835

600000

331.609

331.3933

Applying the result to an operating site

Keep the layer index fixed when comparing alternative exchanger layouts. The same inlet duty can create different local stratification. A whole-tank energy balance and a layer-temperature comparison answer different design questions.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.