The tank temperature for two exchanger locations starts at 20 °C and finishes at 58.459 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 20 °C and 58.459 °C.
What the reference test measures
The Buildings model named HeatExchangerLocation comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 600,000 seconds. Industry Applied extracted 101 checkpoints for tan_aTop.vol[1].T and kept the original signed values. The regular output spacing is 6,000 seconds. The solver may take different internal steps.
The model definition identifies tan_aTop (Tank), tan_bTop (Tank), watInTan (Boundary p T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Settings to preserve when repeating the experiment
The published test declares senTan_aTop.tau = 0, senTan_bTop.tau = 0. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
At 264,000 seconds, tan_aTop.vol[1].T is 323.812 and tan_bTop.vol[1].T is 323.33. Subtracting the second channel from the first gives +0.482 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.
![Tank temperature for two exchanger locations. In the simulated HeatExchangerLocation case, tan_aTop.vol[1].T ranges from 293.15 to 331.609 K over 600,000 seconds.](https://static.wixstatic.com/media/21e41b_caa9f0d813124f87a2e6832e85fd39ce~mv2.png/v1/fill/w_616,h_345,al_c,q_85,enc_auto/21e41b_caa9f0d813124f87a2e6832e85fd39ce~mv2.png)
Reproducing the largest recorded change
Between the stored points at 6,000 and 12,000 seconds, tan_aTop.vol[1].T changes from 294.341 to 295.637. Subtracting the earlier reading gives +1.296 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | tan_aTop.vol[1].T (K) | tan_bTop.vol[1].T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
6000 | 294.3413 | 294.3347 |
12000 | 295.6369 | 295.6302 |
150000 | 315.7006 | 315.3485 |
300000 | 325.475 | 325.0003 |
450000 | 329.7349 | 329.3835 |
600000 | 331.609 | 331.3933 |
Applying the result to an operating site
Keep the layer index fixed when comparing alternative exchanger layouts. The same inlet duty can create different local stratification. A whole-tank energy balance and a layer-temperature comparison answer different design questions.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Daniel Dan, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.