The THwSup.T trace covers 22.548 to 50 °C, a temperature span of 27.452 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TableData2DLoadDepSHC. The source file places it under Fluid, Heat Pumps, Modular Reversible. We used the 101 stored values for THwSup.T over the interval 0 to 5,400 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name THeaWatSet (Sin), THwEnt (Constant), TChwEnt (Constant), TOut (Constant). The source declares THwSup_nominal = 323.15, THwRet_nominal = 315.15, TChwSup_nominal = 280.15, TChwRet_nominal = 285.15. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel THwRet.T covers 311.426 to 315.15 K. At 54 s, the primary value is 295.698 and the companion is 311.446. Their signed difference is -15.749 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Table data2 d load dep shc. The simulated THwSup.T channel runs from 295.698 to 323.15 K over 5,400 seconds.
Table data2 d load dep shc. The simulated THwSup.T channel runs from 295.698 to 323.15 K over 5,400 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 54 seconds. Subtracting 323.15 from 295.698 gives -27.452 K. Its location brackets the change within one saved interval of 54 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

THwSup.T (K)

THwRet.T (K)

0

323.15

315.15

54

295.6978

311.4464

1080

322.0677

311.4259

2160

320.5764

311.4259

3240

323.1164

311.4259

4320

323.15

311.4259

5400

319.6427

311.4259

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.