The damValFan1.TDis trace covers 11.802 to 14.198 °C, a temperature span of 2.395 K. The first recorded maximum occurs at 864 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named DamperValves. The source file places it under Controls, OBC, ASHRAE, G36, Terminal Units, Parallel Fan CVF, Subsequences. We used the 101 stored values for damValFan1.TDis over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name damValFan1 (Damper Valves), uCoo (Ramp), TZon (Constant), VActMin_flow (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel damValFan1.TSup covers 285.152 to 287.148 K. At 2,664 s, the primary value is 284.952 and the companion is 285.152. Their signed difference is -0.1996 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 72 seconds. Subtracting 286.15 from 286.3 gives 0.1504 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | damValFan1.TDis (K) | damValFan1.TSup (K) |
|---|---|---|
0 | 286.15 | 286.15 |
72 | 286.3004 | 286.2753 |
864 | 287.3476 | 287.148 |
1440 | 286.8553 | 286.7378 |
2664 | 284.9524 | 285.152 |
2880 | 285.0087 | 285.1989 |
4320 | 287.2913 | 287.101 |
5760 | 285.4447 | 285.5622 |
7200 | 286.15 | 286.15 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.