The senTanDyn.T trace covers 20 to 55.458 °C, a temperature span of 35.458 K. The first recorded maximum occurs at 11,664 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named HeatExchangerDynamics. The source file places it under Fluid, Storage. We used the 101 stored values for senTanDyn.T over the interval 0 to 14,400 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name watInTan (Boundary p T), mHex_flow1 (Mass Flow Source T), tanDyn (Tank), tanSte (Tank). The source declares QHex_flow_nominal = 2000. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTanSte.T covers 293.15 to 328.613 K. At 1,008 s, the primary value is 296.155 and the companion is 313.54. Their signed difference is -17.385 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Stratified tank with steady-state and dynamic heat exchanger balance. The simulated senTanDyn.T channel runs from 293.15 to 328.608 K over 14,400 seconds.
Stratified tank with steady-state and dynamic heat exchanger balance. The simulated senTanDyn.T channel runs from 293.15 to 328.608 K over 14,400 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 1,008 to 1,152 seconds. Subtracting 296.155 from 316.627 gives 20.472 K. Its location brackets the change within one saved interval of 144 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTanDyn.T (K)

senTanSte.T (K)

0

293.15

293.15

1008

296.1549

313.5402

1152

316.6266

317.07

2880

325.8979

325.91

5760

323.5468

323.4863

8640

323.6304

323.719

11520

328.5526

328.5578

11664

328.608

328.6131

14400

312.4503

312.2843

What to check on site

Identify the stored quantity and the boundary through which energy or mass enters. A layer temperature, outlet temperature and volume mean describe different states. Preserve initial inventory and the sequence of charge or discharge when repeating the case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.