The recorded simpleConsumer.Q_flow channel spans -5,869 to -2,000 W in this reference run. It starts at -2,000 and ends at -5,869. The first recorded maximum occurs at 0 seconds and the first minimum at 38,200 seconds.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named StorageSimpleExample. The source file places it under Fluid, Storage. We used the 101 stored values for simpleConsumer.Q_flow over the interval 0 to 38,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name storageSimple (Storage Simple), pumpCon (Speed Controlled y), PIDHR (Lim PID), PelHR (Real Output). The source declares dp_nominal_hr = 1000, dT_gen = 8, bandwidth = 5. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel storageSimple.layer[1].T starts at 308.15, ends at 308.842 and has a recorded range of 302.044 to 311.869 K. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Storage simple. The simulated simpleConsumer.Q_flow channel runs from -5,869 to -2,000 W over 38,200 seconds.
Storage simple. The simulated simpleConsumer.Q_flow channel runs from -5,869 to -2,000 W over 38,200 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed simpleConsumer.Q_flow samples by the trapezoidal rule gives -39.728 kWh over 38,200 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

simpleConsumer.Q_flow (W)

storageSimple.layer[1].T (K)

0

-2000

308.15

7640

-2300.828

310.0777

15280

-3112.815

309.9006

21392

-3969.749

310.6973

21774

-4025.307

310.2729

22920

-4191.691

309.5142

30560

-5212.902

309.7187

38200

-5869.238

308.8418

What to check on site

Identify the stored quantity and the boundary through which energy or mass enters. A layer temperature, outlet temperature and volume mean describe different states. Preserve initial inventory and the sequence of charge or discharge when repeating the case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.