The recorded steTra.m_flow channel spans 0 to 10 kg/s in this reference run. It starts at 0 and ends at 10. The first recorded maximum occurs at 120.6 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named SteamTrap. The source file places it under DHC, Loads, Steam. We used the 101 stored values for steTra.m_flow over the interval 0 to 180 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name ram (Ramp), sou (Boundary p T), sin (Boundary p T), steTra (Steam Trap). The source declares TSatHig = 273.15+110, TSatLow = 273.15+100, pSat = 143380, m_flow_nominal = 10. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel steTra.QLos_flow starts at 0, ends at -419,475 and has a recorded range of -419,475 to 0 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Steam trap. The simulated steTra.m_flow channel runs from 0 to 10 kg/s over 180 seconds.
Steam trap. The simulated steTra.m_flow channel runs from 0 to 10 kg/s over 180 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 180 seconds gives a net 899.703 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

steTra.m_flow (kg/s)

steTra.QLos_flow (W)

0

0

0

36

0

0

72

1.995

-83685.32

108

7.995

-335370.5

109.8

8.295

-347954.7

111.6

8.595001

-360539

120.6

10

-419475.3

144

10

-419475.3

180

10

-419475.3

What to check on site

Compare fuel or electrical input with useful heat at a declared delivery boundary. Include the warm-up interval and any period on standby. Separate a temperature setpoint from the measured outlet and keep auxiliary energy in a stated part of the balance.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.