The recorded hum.sta_b.T temperature spans 20 °C to 20.664 °C in this simulation. That is a change of 0.66376 K. The first saved maximum occurs at 464.4 s. The source trace and download retain absolute temperatures in kelvin.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named SteamHumidifier_X_dynamic. The source file places it under Fluid, Humidifiers. We used the 101 stored values for hum.sta_b.T over the interval 0 to 1,080 seconds. This is a simulated test with specified inputs and boundaries.
The reference file contains 5 recorded variables. Alongside the primary output there are XSet.y[1], senHum.X, hum.sta_a.T, hum.sta_b.T, hum.mWat_flow. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.
Compare the recorded channels
At 561.6 s, hum.sta_b.T reads 293.431 K and senHum.X reads 0.010577 kg/kg. Across the run, the second channel ranges from 0.010001 kg/kg to 0.013999 kg/kg. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 550.8 to 561.6 seconds. Subtracting 293.673 from 293.431 gives -0.242 K. Its location brackets the change within one saved interval of 10.8 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | hum.sta_b.T (K) | senHum.X (kg/kg) |
|---|---|---|
0 | 293.15 | 0.010001 |
216 | 293.4402 | 0.01194642 |
432 | 293.8133 | 0.013999 |
464.4 | 293.8138 | 0.013999 |
550.8 | 293.6726 | 0.01169621 |
561.6 | 293.4306 | 0.01057692 |
648 | 293.1503 | 0.010001 |
864 | 293.1502 | 0.010001 |
1080 | 293.1502 | 0.010001 |
What to check on site
Compare fuel or electrical input with useful heat at a declared delivery boundary. Include the warm-up interval and any period on standby. Separate a temperature setpoint from the measured outlet and keep auxiliary energy in a stated part of the balance.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Units in the source model
The component declarations identify the scale of the exported variables. In this run, senHum.X uses kg/kg. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.