The recorded heaPum.P channel spans 3,673 to 6,499 W in this reference run. It starts at 3,673 and ends at 6,499. The first recorded maximum occurs at 1,000 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ScrollWaterToWater_Static. The source file places it under Fluid, Heat Pumps. We used the 101 stored values for heaPum.P over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sin2 (Boundary p T), sin1 (Boundary p T), isOn (Constant), loa (Mass Flow Source T). The source declares m1_flow_nominal = 0.47, m2_flow_nominal = 0.47, flowSource = 0.79, flowLoad = 0.47. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel heaPum.QCon_flow starts at 17,327, ends at 25,393 and has a recorded range of 17,327 to 26,245 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Static scroll water-to-water heat pump. The simulated heaPum.P channel runs from 3,673 to 6,499 W over 1,000 seconds.
Static scroll water-to-water heat pump. The simulated heaPum.P channel runs from 3,673 to 6,499 W over 1,000 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed heaPum.P samples by the trapezoidal rule gives 1.316 kWh over 1,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

heaPum.P (W)

heaPum.QCon_flow (W)

0

3673.319

17326.78

200

3733.827

19952.61

400

4230.575

22332.03

600

4954.319

24596.34

740

5520.219

26137.88

750

5562.531

26245.44

800

5742.392

26081.33

1000

6498.959

25392.93

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.