The recorded heaPum.P channel spans 1,683 to 2,925 W in this reference run. It starts at 1,709 and ends at 2,925. The first recorded maximum occurs at 1,000 seconds and the first minimum at 250 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ReciprocatingWaterToWater_Static. The source file places it under Fluid, Heat Pumps. We used the 101 stored values for heaPum.P over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name heaPum (Reciprocating Water To Water), sin2 (Boundary p T), sin1 (Boundary p T), loa (Mass Flow Source T). The source declares m1_flow_nominal = 0.47, m2_flow_nominal = 0.47, flowSource = 0.79, flowLoad = 0.47. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel heaPum.QCon_flow starts at 9,369, ends at 13,545 and has a recorded range of 9,369 to 13,911 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
Integrating the signed heaPum.P samples by the trapezoidal rule gives 0.5872 kWh over 1,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | heaPum.P (W) | heaPum.QCon_flow (W) |
|---|---|---|
0 | 1708.938 | 9369.306 |
200 | 1692.797 | 10648.23 |
250 | 1683.048 | 10977.62 |
400 | 1882.914 | 11860.74 |
600 | 2182.58 | 13040.42 |
800 | 2531.304 | 13843.28 |
990 | 2905.376 | 13560.68 |
1000 | 2925.103 | 13544.52 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.