The published pump_y.m_flow signal spans 0 to 1.601 kg/s in the reference run. It starts at 0 and finishes at 1.601. The signed change between those endpoint samples is +1.601 kg/s.
What the reference test measures
The AixLib model named MoverStages comes from the RWTH Aachen University E.ON Energy Research Center. The saved result covers simulation time 0 to 1 seconds. Industry Applied extracted 101 checkpoints for pump_y.m_flow and kept the original signed values. The regular output spacing is 0.01 seconds. The solver may take different internal steps.
The model declares m_flow_nominal = 2, dp_nominal = 10000. These are source-model settings. They describe this particular run and must be carried forward if comparing another implementation.
Settings to preserve when repeating the experiment
The published test declares m_flow_nominal = 2, dp_nominal = 10000. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
At 0.61 seconds, pump_y.m_flow is 1.601 and pump_Nrpm.m_flow is 1.779. Subtracting the second channel from the first gives -0.178 kg/s, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Reproducing the largest recorded change
Between the stored points at 0.6 and 0.61 seconds, pump_y.m_flow changes from 0.8 to 1.601. Subtracting the earlier reading gives +0.801 kg/s. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | pump_y.m_flow (kg/s) | pump_Nrpm.m_flow (kg/s) |
|---|---|---|
0 | 0 | 0 |
0.25 | 0 | 0 |
0.5 | 0.8003744 | 0.8893297 |
0.6 | 0.8003744 | 0.8893297 |
0.61 | 1.600972 | 1.778883 |
0.75 | 1.600972 | 1.778883 |
1 | 1.600972 | 1.778883 |
Applying the result to an operating site
A stage number is a command, not a measured flow. Match speed fractions, pressure targets and any minimum operating restrictions before comparing stage transitions. A sudden flow jump can reflect a control mapping rather than a mechanical fault.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.