The borFieUTubWitTou.sta_a.T trace covers 5.027 to 14.973 °C, a temperature span of 9.945 K. The first recorded maximum occurs at 2,880 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Borefield. The source file places it under Fluid, Geothermal, Borefields, TOUGH. We used the 101 stored values for borFieUTubWitTou.sta_a.T over the interval 0 to 72,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name floRat (Sin), watTem (Sin), sou (Mass Flow Source T), borFieUTubWitTou (One U Tube). The source declares TGro = 283.15. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel borFieUTubWitTou.sta_b.T covers 281.164 to 286.403 K. At 61,920 s, the primary value is 278.177 and the companion is 285.807. Their signed difference is -7.63 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Single u-tube borefield with ground responses calculated by tough simulation. The simulated borFieUTubWitTou.sta_a.T channel runs from 278.177 to 288.123 K over 72,000 seconds.
Single u-tube borefield with ground responses calculated by tough simulation. The simulated borFieUTubWitTou.sta_a.T channel runs from 278.177 to 288.123 K over 72,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 5,040 to 5,760 seconds. Subtracting 284.19 from 282.11 gives -2.079 K. Its location brackets the change within one saved interval of 720 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

borFieUTubWitTou.sta_a.T (K)

borFieUTubWitTou.sta_b.T (K)

0

283.15

283.15

2880

288.1226

283.5857

5040

284.1895

283.7575

5760

282.1104

283.175

7920

278.1774

281.3501

14400

287.4801

283.0976

28800

278.8199

283.6441

43200

283.15

284.9933

57600

287.4801

285.4373

72000

278.8199

283.7986

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.