The relFanCon.dpBui trace ranges from 11 Pa to 14 Pa across 101 saved checkpoints. It begins at 11 Pa and finishes at 14 Pa after 3,600 s of test time. The source identifies the channel scale as Pa. Its first saved maximum occurs at 1,800 s.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ReliefFan. The source file places it under Controls, OBC, ASHRAE, G36, AH Us, Multi Zone, variable air volume, Set Points. We used the 101 stored values for relFanCon.dpBui over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name relFanCon (Relief Fan), relFanCon1 (Relief Fan), relFanCon2 (Relief Fan), supFan (Pulse). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 1,800 s, relFanCon.dpBui is 14 Pa and relFanCon1.dpBui is 40 Pa. Subtracting the second value from the first gives -26 Pa. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 216 to 252 seconds. Subtracting 11.36 from 11.42 gives 0.06 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | relFanCon.dpBui (Pa) | relFanCon1.dpBui (Pa) |
|---|---|---|
0 | 11 | 0 |
216 | 11.36 | 4.8 |
252 | 11.42 | 5.6 |
720 | 12.2 | 16 |
1440 | 13.4 | 32 |
1800 | 14 | 40 |
2160 | 14 | 40 |
2880 | 14 | 40 |
3600 | 14 | 40 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Units in the source model
The component declarations identify the scale of the exported variables. In this run, relFanCon.dpBui uses Pa and relFanCon1.dpBui uses Pa. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.

