The recorded minCon.dpMinOutDam channel spans 120 to 172 source units in this reference run. It starts at 120 and ends at 172. The first recorded maximum occurs at 1,800 seconds and the first minimum at 0 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named SeparateWithDP. The source file places it under Controls, OBC, ASHRAE, G36, AH Us, Multi Zone, variable air volume, Economizers, Subsequences, Limits. We used the 101 stored values for minCon.dpMinOutDam over the interval 0 to 1,800 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name disMinCon (Separate With differential pressure), disMinCon1 (Separate With differential pressure), minCon (Separate With differential pressure), VOutMinSet_flow (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel disMinCon.dpMinOutDam covers 250 to 350 source units. At 1,800 s, the primary value is 172 and the companion is 350. Their signed difference is -178 source units, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 126 to 144 seconds. Subtracting 123.64 from 124.16 gives 0.52 source units. Its location brackets the change within one saved interval of 18 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | minCon.dpMinOutDam (source units) | disMinCon.dpMinOutDam (source units) |
|---|---|---|
0 | 120 | 250 |
126 | 123.64 | 257 |
144 | 124.16 | 258 |
360 | 130.4 | 270 |
720 | 140.8 | 290 |
1080 | 151.2 | 310 |
1440 | 161.6 | 330 |
1800 | 172 | 350 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.