The senExhTem.T trace covers 20 to 35.997 °C, a temperature span of 15.997 K. The first recorded maximum occurs at 360 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named SpeedControlled. The source file places it under Fluid, Heat Exchangers, Thermal Wheels, Sensible. We used the 101 stored values for senExhTem.T over the interval 0 to 360 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sin_2 (Boundary p T), sou_2 (Boundary p T), TSup (Ramp), sin_1 (Boundary p T). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senSupTem.T covers 293.15 to 297.656 K. At 360 s, the primary value is 309.147 and the companion is 297.18. Their signed difference is 11.967 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Sensible heat recovery wheel with a variable-speed drive. The simulated senExhTem.T channel runs from 293.15 to 309.147 K over 360 seconds.
Sensible heat recovery wheel with a variable-speed drive. The simulated senExhTem.T channel runs from 293.15 to 309.147 K over 360 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 3.6 seconds. Subtracting 293.15 from 300.698 gives 7.548 K. Its location brackets the change within one saved interval of 3.6 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senExhTem.T (K)

senSupTem.T (K)

0

293.15

293.15

3.6

300.6985

295.3416

72

302.3328

295.8161

144

308.67

297.6561

216

308.715

297.6112

288

308.931

297.3955

360

309.147

297.1799

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.