The recorded ter.QActHea_flow channel spans 0 to 2,085 W in this reference run. It starts at 0 and ends at 2,085. The first recorded maximum occurs at 1,000 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TerminalUnitScaling. The source file places it under DHC, Loads. We used the 101 stored values for ter.QActHea_flow over the interval 0 to 1,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name supHeaWat (Mass Flow Source T), sinHeaWat (Boundary p T), ter (Fan Coil2 Pipe Heating), TSet (Constant). The source declares facMul = 2. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel terUniMulZonMul.QActHea_flow covers 0 to 4,169 W. At 1,000 s, the primary value is 2,085 and the companion is 4,169. Their signed difference is -2,085 W, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Scaling factor of the terminal unit. The simulated ter.QActHea_flow channel runs from 0 to 2,085 W over 1,000 seconds.
Scaling factor of the terminal unit. The simulated ter.QActHea_flow channel runs from 0 to 2,085 W over 1,000 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed ter.QActHea_flow samples by the trapezoidal rule gives 0.4398 kWh over 1,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

ter.QActHea_flow (W)

terUniMulZonMul.QActHea_flow (W)

0

0

0

100

459.4271

918.8542

110

507.0203

1014.041

200

930.2176

1860.435

400

1823.922

3647.844

600

2007.592

4015.183

800

2050.938

4101.875

1000

2084.692

4169.384

What to check on site

Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.