The signed flow trace gives a net 57.06 kg over 3,600 s, using the trapezoidal rule between saved samples. The smallest and largest reported rates are 0.001 kg/s and 0.1 kg/s. Check the positive flow direction in the model before using the sign to describe delivery or return.

The two port readings belong to the coil’s different fluid streams. Integrate a signed mass-flow rate over its own time axis to calculate the mass passing that side. The resulting difference between airstream and liquid-stream mass is not the condensate collected. A condensate calculation needs a moisture balance on the air side.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named WetCoilEffectivenessNTUMassFlow. The source file places it under Fluid, Heat Exchangers. We used the 101 stored values for hex.port_a1.m_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name hex (Wet Coil Effectiveness NTU), senRelHum (Relative Humidity Two Port). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 2,160 s, hex.port_a1.m_flow is 0.001 kg/s and hex.port_a2.m_flow is -0.14 kg/s. Subtracting the second value from the first gives 0.141 kg/s. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

How much mass passes each side of a wet cooling coil. The simulated hex.port_a1.m_flow channel runs from 0.001 to 0.1 kg/s over 3,600 seconds.
How much mass passes each side of a wet cooling coil. The simulated hex.port_a1.m_flow channel runs from 0.001 to 0.1 kg/s over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 3,600 seconds gives a net 57.06 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hex.port_a1.m_flow (kg/s)

hex.port_a2.m_flow (kg/s)

0

0.1

0.14

432

0.0802

0.14

468

0.0703

0.14

720

0.001

0.14

1440

0.001

0.14

2160

0.001

-0.14

2880

0.001

0

3600

0.001

0

What to check on site

Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.