The recorded sla.sta_b.T temperature spans 20 °C to 24.741 °C in this simulation. That is a change of 4.7407 K. The first saved maximum occurs at 86,400 s. The source trace and download retain absolute temperatures in kelvin.
The fluid-side and surface temperatures are distinct states. After the driving condition changes, compare when each begins to move and how far each has moved at the same saved time. This separates the surface response from a change seen only by the fluid.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named StepResponseEpsilonNTU. The source file places it under Fluid, Heat Exchangers, Radiant Slabs. We used the 101 stored values for sla.sta_b.T over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name sin (Boundary ph), sou (Mass Flow Source T), sla (Single Circuit Slab), TAirAbo (Fixed Temperature). The source declares m_flow_nominal = 0.167, A = 10. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 44,064 s, sla.sta_b.T is 297.254 K and sla.surf_a.T is 293.198 K. Subtracting the second value from the first gives 4.0566 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 43,200 to 44,064 seconds. Subtracting 293.15 from 297.254 gives 4.104 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | sla.sta_b.T (K) | sla.surf_a.T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
17280 | 293.15 | 293.15 |
34560 | 293.15 | 293.15 |
43200 | 293.15 | 293.15 |
44064 | 297.2544 | 293.1977 |
51840 | 297.7507 | 295.2416 |
69120 | 297.8837 | 295.9918 |
86400 | 297.8907 | 296.0287 |
What to check on site
Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.