The borHol.sta_a.T trace covers 10 to 25 °C, a temperature span of 15 K. The first recorded maximum occurs at 9,460,800 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named UTube. The source file places it under Fluid, Geothermal, Boreholes. We used the 101 stored values for borHol.sta_a.T over the interval 0 to 157,680,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name borHol (U Tube), sin (Boundary ph), sou (Mass Flow Source T). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel borHol.sta_b.T covers 283.15 to 294.548 K. At 9,460,800 s, the primary value is 298.15 and the companion is 293.669. Their signed difference is 4.481 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

S the borehole. The simulated borHol.sta_a.T channel runs from 283.15 to 298.15 K over 157,680,000 seconds.
S the borehole. The simulated borHol.sta_a.T channel runs from 283.15 to 298.15 K over 157,680,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 7,884,000 to 9,460,800 seconds. Subtracting 283.15 from 298.15 gives 15 K. Its location brackets the change within one saved interval of 1,576,800 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

borHol.sta_a.T (K)

borHol.sta_b.T (K)

0

293.15

293.15

7884000

283.1504

283.1504

9460800

298.15

293.6686

3.1536e+07

284.2643

284.2643

6.3072e+07

284.5653

284.5653

9.4608e+07

284.7364

284.7364

1.26144e+08

284.8548

284.8548

1.5768e+08

284.946

284.946

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.