The hex.vol1.T trace covers 10 to 29.357 °C, a temperature span of 19.357 K. The first recorded maximum occurs at 3,600 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

These temperatures belong to the two internal fluid volumes of one borehole element. Compare them at the same time to locate a difference within the heat exchanger. A surrounding soil or borehole-wall temperature would tell you something different about the path the heat takes.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named HexInternalElement. The source file places it under Fluid, Geothermal, Boreholes. We used the 101 stored values for hex.vol1.T over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 4 recorded variables. Alongside the primary output there are hex.vol1.T, hex.vol2.T, hex.vol1.heatPort.Q_flow, hex.vol2.heatPort.Q_flow. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel hex.vol2.T covers 283.15 to 301.918 K. At 72 s, the primary value is 294.18 and the companion is 287.149. Their signed difference is 7.031 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Comparing the two fluid temperatures inside a modelled borehole element. The simulated hex.vol1.T channel runs from 283.15 to 302.507 K over 3,600 seconds.
Comparing the two fluid temperatures inside a modelled borehole element. The simulated hex.vol1.T channel runs from 283.15 to 302.507 K over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 36 seconds. Subtracting 283.15 from 289.982 gives 6.832 K. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

hex.vol1.T (K)

hex.vol2.T (K)

0

283.15

283.15

36

289.9818

284.5049

720

301.2668

299.5298

1440

301.7104

300.3897

2160

302.0497

301.0404

2880

302.3091

301.5377

3600

302.5073

301.9178

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.