The published floMac1.dp signal spans -2,000 to 400.6 Pa in the reference run. It starts at -2,000 and finishes at 1. The signed change between those endpoint samples is +2,001 Pa.

What the reference test measures

The Buildings model named PumpsSeries comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 300 seconds. Industry Applied extracted 101 checkpoints for floMac1.dp and kept the original signed values. The regular output spacing is 3 seconds. The solver may take different internal steps.

The model definition identifies floMac1 (Speed Controlled y), floMac2 (Speed Controlled y). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares m_flow_nominal = 1. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 174 seconds, floMac1.dp is 400.6 and floMac2.dp is -4,400.6. Subtracting the second channel from the first gives +4,801.2 Pa, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Pressure rise across series pumps. In the simulated PumpsSeries case, floMac1.dp ranges from -2,000 to 400.6 Pa over 300 seconds.
Pressure rise across series pumps. In the simulated PumpsSeries case, floMac1.dp ranges from -2,000 to 400.6 Pa over 300 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 150 and 153 seconds, floMac1.dp changes from -2,000 to -1,515.717. Subtracting the earlier reading gives +484.283 Pa. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

floMac1.dp (Pa)

floMac2.dp (Pa)

0

-2000

-2000

75

-2000

-2000

150

-2000

-2000

153

-1515.717

-2484.283

174

400.5999

-4400.6

225

0.9997501

-4001

300

0.9997501

-4001

Applying the result to an operating site

Series machines share the throughflow in an unbranched line and contribute separate pressure changes. Keep the orientation of each pressure difference with its reading. The system operating point can move while the pumps’ combined head changes.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.