The fan1.dp trace ranges from -526.218 Pa to 0 Pa across 101 saved checkpoints. It begins at 0 Pa and finishes at 0 Pa after 600 s of test time. The source identifies the channel scale as Pa. Its first saved maximum occurs at 0 s.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ControlledFlowMachinePreconfigured. The source file places it under Fluid, Movers, Preconfigured. We used the 101 stored values for fan1.dp over the interval 0 to 600 seconds. This is a simulated test with specified inputs and boundaries.
The source declares m_flow_nominal = 2, dp_nominal = 500. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 324 s, fan1.dp is -21.681 Pa and fan2.dp is -24.715 Pa. Subtracting the second value from the first gives 3.0336 Pa. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 60 to 66 seconds. Subtracting -526.218 from -336.813 gives 189.404 Pa. Its location brackets the change within one saved interval of 6 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | fan1.dp (Pa) | fan2.dp (Pa) |
|---|---|---|
0 | 0 | 0 |
36 | -526.2176 | -526.2176 |
60 | -526.2176 | -526.2176 |
66 | -336.8131 | -337.615 |
120 | 0 | -2.910383e-11 |
240 | 0 | 0 |
360 | 0 | 0 |
480 | 0 | 0 |
600 | 0 | 0 |
What to check on site
Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.